Remote Terminal Panels

Optional DIN rail mounted Remote Terminal Panels (RTPs) are available for use with pre-wired cables to reduce installation

time and labor expense. Three types of RTPs are available: analog inputs, relay outputs, and other I/O modules. Three cable

lengths are also available to match hardware to installation variations. Analog inputs RTPs include transmitter shunt resistors

and transmitter power terminals with individual circuit fuses. The Relay Output RTP includes a fuse and power disconnect

switch for each output. All the three types of RTP panels also switch power to allow module removal and installation under

controller power. See page 34.

Terminal Blocks

20-screw Barrier style and Euro style terminal blocks are available for use with all ControlEdge HC900 I/O Modules.

Red terminal blocks are used for high voltage connections for added safety while black terminal blocks are used for low

voltage connections. A 36-terminal Euro style block is available with the 16 AI, the 8 and 16 AO as well as the 32 DC DI and

32 DC DO module types. See page 27.

Specifications for modules

I/O Module Attributes

Remove & Insert under power

Standard. Modules are automatically sensed and configured on insertion. Field power

shall be disconnected before removing field terminal blocks.

LED Channel State indicators

Via light pipes at front of module, one state LED for each digital I/O point – green

indicates ON, logic side

LED Module Status indicator

Via light pipe, one per module, tri-color to represent module status, Green = OK, Red

= Fault (# of flashes indicates fault), Amber = Override (Force)

I/O Labels

51304453-100

Color-coded, on module door, removable, with write-on area to label I/O

Processor

Micro-controller per module for parallel processing

Terminal Boards

20 screw: Barrier or Euro style, tin-plated or gold-plated (for DC connections)

36 screw: Euro style gold plated (Required with certain higher capacity modules)

Keying

Hardware keying matches each module to its terminal block with its field wiring.

Environmental and Vibration Specifications

51304453-100

Mounting

Standard 35mm wide DIN Rail

Provides connection of field wiring to controller I/O within an enclosure only.

Dimensions

4.38” (111.1 mm) x 3.70” (94.0mm) x 2.60” (66.0mm) (L x W x H)

Vibration

Amplitude

Acceleration

Vibration

5Hz to 15.77Hz, 2.03mm (0.08”) amplitude (peak to peak)

15.77 to 250Hz, 1.0-g

Sweeping, at rate of .33 octave/min.

Tray material

Tray and end caps

Flammability

Polyvinyl Chloride (PVC)

UL94-V0

Environmental

Temperature

Relative Humidity

Harsh Environment **

ROHS**

** Except PSU module

Operating: 0 deg. C (32F) to 60 deg. C (140F)

Storage: -40 deg. C (140F) to 70 deg. C (158F)

Operating: 10% to 90% Non-condensing

Storage: 5% to 95% Non-condensing

All the modules including CPU, Scanner, PSU, RTP, Backplane, RSM/PSM, and

Backplanes have conformal coating that is suitable for operation in G3 level of harsh

environment.

Entire system is compliant to RoHS 2 directive

ControlEdge 900 Platform Modules 3

Certifications

CE

EN61326-1:2013. EN61326-3-1:2008. EN55011:2009/A1.2010.

EN61010-1:2010

UL Certificate:  E201698

UL Listed- Process Control Equipment, Electrical UL 61010-1 2nd Edition

ATEX Certificate:  HON 08.0201

II 3 G Ex nA IIC T* Gc

EN 60079-0:  2011; EN 60079-15: 2010

CSA Certificate:  1367757

Class I, Division 2. Groups A, B, C D; T*

CAN/ CSA C22.2 No. 0-M91; CAN/ CSA C22.2 No. 94-M94;

CAN/ CSA C22.2 No 1010.1-92; CAN/ CSA C22.2 No 1010.1B-97;

CSA C22.2 No. 213-M1987

FM Certificate:  3011798

Class 1. Div. 2 Groups A, B, C, D; T*

FM 3600:  2010; FM 3611:  2004; FM 3810:  2005

*  Module Temperature: Classifications T3 to T6

Cables

High voltage

Low voltage

Lengths: 1.0. 2.5. 5.0 meters. Cable power is limited to 24 Amps per module at 60C

(140 degrees F) and 32 Amps at 54C (129 degrees F).

Lengths: 1.0. 2.5. 5.0 meters.

I/O module Compliance

CE Conformity This product is in conformity with the protection requirements of the following

European Council Directives:

2006/ 95/ EC, the Low Voltage Directive (evaluated to EN61010-1:2010)

2004/108/EC, the EMC Directive (evaluated to EN61326-1:2013). Conformity of this

product with any other European Council Directive(s) shall not be assumed.

General Purpose Safety Compliant with EN61010-1. UL61010-1 2nd Edition, CSA C22.2 No. 1010-1

Hazardous (Classified)

Location Safety

FM Class 1. Div. 2. Groups A, B, C, D

Class 1. Zone 2. IIC