F7133 | HIMA | 4-Fold Power Distribution
Manufacturer : HIMA
Product No. : F7133
Product Type : 4-Fold Power Distribution
Fuses : Max. 4 A slow blow
Switching time : Approx. 100 ms (relay)
Load ability of the relay contacts : 30 V/4 A (continuous load)
Residual voltage in case of fuse tripped : 0 V
Residual current in case of fuse tripped : 0 mA
Residual voltage in case missing supply : Max. 3 V
Residual current in case of missing supply : < 1 mA
Space requirement : 4 TE
Operating data : 24 V DC : 60 mA
Shipping Weight : 2 Kg
LED Indicators
The light-emitting diodes (LEDs) indicate the operating state of the controller. The LEDs are
classified as follows:
Operating voltage LED
System LEDs
Name
Communication LEDs
I/O LEDs
F7133
Function and meaning of the system LEDs and communication LEDs depend on the CPU
operating system (and thus on the COM operating system).
When the supply voltage is switched on, a LED test is performed and all LEDs are briefly lit.
Definition of Blinking Frequencies
The following table defines the blinking frequencies of the LEDs
The key can be accessed through a small round hole located approximately 5 cm from the
upper left-hand side of the housing. The key is engaged using a suitable pin made of insulating
material to avoid short-circuits within the controller.
The reset is only effective if the controller is rebooted (switched off and on) while the key is
simultaneously engaged for at least 20 s. Engaging the key during operation has no effect.
Properties and behavior of the controller after a reboot with engaged reset key:
Connection parameters (IP address and system ID) are set to the default values.
All accounts are deactivated except for the administrator default account with empty
password.

F7133
With COM operating system version 10.42 and higher, loading a user program or operating
system with default connection parameters is inhibited!
The loading procedure is only allowed after the connection parameters and the account have
been configured on the controller and the controller has been rebooted.
After a new reboot without the reset key engaged, the connection parameters (IP address and
system ID) and accounts become effective.
Those configured by the user.
Those valid prior to rebooting with the reset key engaged, if no changes were performed.