Remote Terminal Panels
Optional DIN rail mounted Remote Terminal Panels (RTPs) are available for use with pre-wired cables to reduce installation
time and labor expense. Three types of RTPs are available: analog inputs, relay outputs, and other I/O modules. Three cable
lengths are also available to match hardware to installation variations. Analog inputs RTPs include transmitter shunt resistors
and transmitter power terminals with individual circuit fuses. The Relay Output RTP includes a fuse and power disconnect
switch for each output. All the three types of RTP panels also switch power to allow module removal and installation under
controller power. See page 34.
Terminal Blocks
20-screw Barrier style and Euro style terminal blocks are available for use with all ControlEdge HC900 I/O Modules.
Red terminal blocks are used for high voltage connections for added safety while black terminal blocks are used for low
voltage connections. A 36-terminal Euro style block is available with the 16 AI, the 8 and 16 AO as well as the 32 DC DI and
32 DC DO module types. See page 27.
Specifications for modules
I/O Module Attributes
Remove & Insert under power
Standard. Modules are automatically sensed and configured on insertion. Field power
shall be disconnected before removing field terminal blocks.
LED Channel State indicators
Via light pipes at front of module, one state LED for each digital I/O point – green
indicates ON, logic side
LED Module Status indicator
Via light pipe, one per module, tri-color to represent module status, Green = OK, Red
= Fault (# of flashes indicates fault), Amber = Override (Force)
I/O Labels
51304453-100
Color-coded, on module door, removable, with write-on area to label I/O
Processor
Micro-controller per module for parallel processing
Terminal Boards
20 screw: Barrier or Euro style, tin-plated or gold-plated (for DC connections)
36 screw: Euro style gold plated (Required with certain higher capacity modules)
Keying
Hardware keying matches each module to its terminal block with its field wiring.
Environmental and Vibration Specifications

51304453-100
Mounting
Standard 35mm wide DIN Rail
Provides connection of field wiring to controller I/O within an enclosure only.
Dimensions
4.38” (111.1 mm) x 3.70” (94.0mm) x 2.60” (66.0mm) (L x W x H)
Vibration
Amplitude
Acceleration
Vibration
5Hz to 15.77Hz, 2.03mm (0.08”) amplitude (peak to peak)
15.77 to 250Hz, 1.0-g
Sweeping, at rate of .33 octave/min.
Tray material
Tray and end caps
Flammability
Polyvinyl Chloride (PVC)
UL94-V0
Environmental
Temperature
Relative Humidity
Harsh Environment **
ROHS**
** Except PSU module
Operating: 0 deg. C (32F) to 60 deg. C (140F)
Storage: -40 deg. C (140F) to 70 deg. C (158F)
Operating: 10% to 90% Non-condensing
Storage: 5% to 95% Non-condensing
All the modules including CPU, Scanner, PSU, RTP, Backplane, RSM/PSM, and
Backplanes have conformal coating that is suitable for operation in G3 level of harsh
environment.
Entire system is compliant to RoHS 2 directive
ControlEdge 900 Platform Modules 3
Certifications
CE
EN61326-1:2013. EN61326-3-1:2008. EN55011:2009/A1.2010.
EN61010-1:2010
UL Certificate: E201698
UL Listed- Process Control Equipment, Electrical UL 61010-1 2nd Edition
ATEX Certificate: HON 08.0201
II 3 G Ex nA IIC T* Gc
EN 60079-0: 2011; EN 60079-15: 2010
CSA Certificate: 1367757
Class I, Division 2. Groups A, B, C D; T*
CAN/ CSA C22.2 No. 0-M91; CAN/ CSA C22.2 No. 94-M94;
CAN/ CSA C22.2 No 1010.1-92; CAN/ CSA C22.2 No 1010.1B-97;
CSA C22.2 No. 213-M1987
FM Certificate: 3011798
Class 1. Div. 2 Groups A, B, C, D; T*
FM 3600: 2010; FM 3611: 2004; FM 3810: 2005
* Module Temperature: Classifications T3 to T6
Cables
High voltage
Low voltage
Lengths: 1.0. 2.5. 5.0 meters. Cable power is limited to 24 Amps per module at 60C
(140 degrees F) and 32 Amps at 54C (129 degrees F).
Lengths: 1.0. 2.5. 5.0 meters.
I/O module Compliance
CE Conformity This product is in conformity with the protection requirements of the following
European Council Directives:
2006/ 95/ EC, the Low Voltage Directive (evaluated to EN61010-1:2010)
2004/108/EC, the EMC Directive (evaluated to EN61326-1:2013). Conformity of this
product with any other European Council Directive(s) shall not be assumed.
General Purpose Safety Compliant with EN61010-1. UL61010-1 2nd Edition, CSA C22.2 No. 1010-1
Hazardous (Classified)
Location Safety
FM Class 1. Div. 2. Groups A, B, C, D
Class 1. Zone 2. IIC