RMP2018
DIGITAL INPUT MODULE
RMP420-Remote Multipurpose
Input/Output
RPM420 is a multipurpose I/O module for use in Alarm monitoring and
Integrated Control Systems. RMP420 is designed for 32 field input channels
in single topologies. Its interface towards the host control computer (RCU) is
provided by redundant I/O bus.
The module is approved for Ex Zone 2 applications.
Functions
• 32 software configurable multipurpose solid-state channels.
• Analog and Digital Input and Output (AI, AO, DI and DO).
• 2 or 3 wire Resistance Temperature Detector (RTD).
• 2 channels can be configured as pulse/frequency/encoder input.
• Short-circuit protected I/O loop power output.
• Dual Remote I/O process BUS interface for redundant communication with
host computer(s).
• Communication ports galvanically insulated from other module circuitry.
• Loop monitoring (per channel)
TECHNICAL DATA
KM Article number RMP420: 306712
Electrical
Input supply voltage: 24 VDC (18-31.2 V)
Power consumption: • Power: 10 W Typical
• Loop power:
Configuration dependable
Power connectors: • Screw terminals
• Cable cross-section:
2.5 mm2
• Max. torque 0.4-0.5 Nm
RBUS interface
RBUS connectors: 2×9 pin male D-Sub,
RS485. galvanic isolated
Input/output
No. of I/O channels: 32
I/O configuration: Multipurpose. Channels
are individually
configured
Digital Input (DI)
Loop voltage: Input supply voltage
Input loop current: Max. 4 mA @ 24 VDC loop
voltage
Channel “Off” current: <0.5 mA
Channel “On” current: >3 mA
Max input voltage: Input supply voltage
Max. input signal freq.: 10 ms pulse
Compliance: Namur compliant, PNP/NPN
compliant
Digital Output (DO)
Loop voltage: Input supply voltage
Loop driver device: Short Circuit Proof High
Side Driver
Loop driver trip current: approx. 1.4 A @ 20˚C
(reset by command)
Loop driver “Off” leakage: Max. 0.1 mA @ 24 VDC
input supply voltage
Loop monitoring current: Max. 2 mA @ 24 VDC input
supply voltage
Analog Input (AI)
Voltage input range: 0-4 V, 0-10 V
Input resistor to ground: 3 MΩ
Current input range: 0-20 mA
Automatic protection: 26 mA
Input resistor to ground: 150 Ω ±1 %
Measurement accuracy: ±0.15% of full scale
PT100 interface
RMP2018
Temp. range:-200 to 600˚C
Resolution: ±0.5˚C
Accuracy: ±0.4% of full scale
Temperature drift: ±50 ppm/˚C
Max. wire resistance: 25 ohm/wire
Response time 1000 ms
Analaog Output (AO)
Voltage output range: 0-10 V ±0.5% (internal
resistance: 1 kohm)
Current output range: 0-20 mA
Minimumlocal resistance: 500 ohm
Measurement accuracy: ±0.35% of full scale
Pulse/Frequency interface
Max. input range: Pulse count freq.:10 kHz

Encoder count Up/Down:
2.5 kHz rev. (4 counts/
revolution)
Duty cycle: Pulse width: min. 11µ @
10 kHz range
Pulse lever transmission: Namur: 1on >2.1 mA, 1off
<1.2 mA. Rin <2.2 kohm,
1max = 3 mA,
Current: 1ohm >9 mA, 1off <7 mA,
Rin <1 kohm, 1max = 13 mA
Accuracy (oscillator): 100 ppm over the whole
temp. range (-15 to
+70˚C) 25 ppm typical @
2˚C
Fail safe
HW Fail safe: Min. 65 ms
Internal Test Error: Instantly set
Soft Fail safe (down
counter):
100 ms – 65 sec. (6 sec.
default)
Compliance • IACS E10
• IEC 60945
• IEC 60355
• IEC/EN60079-0.-7
Type approval Presafe 18ATEX12094X
(II 3G Ex ec IIC T4 Gc)
Environmental specifications
Ambient temp. and humidity:
Temp. operation:-15˚C to +70˚C
Temp. storage:-25˚C to +70˚C
Humidity operation: Up to 98% RH
Humidity storage: Up to 98% RH
Protection standards: IP 20 (IEC 60529)
Mechanical
HxWxD: 355x158x87 mm
Weight: 1.35 kg
DIN rail vertical
mounted: 35 7.5/15
Life cycle prediction
Predicted failure rate @
GB 25˚C (60% confident,
based on chip suppliers
data): 38.5 years
Predicted failure rate @
NS 35˚C (Environmental
derating based on Rome
Laboratory toolkit): 10.4 years